Vacuum Interrupter Integrity Open-Gap Withstand Test

Vacuum Interrupter Integrity Open-Gap Withstand Test

Inspection template for recording high-voltage withstand results across open vacuum interrupter contacts to verify vacuum integrity and identify loss-of-vacuum conditions through withstand failure.

Inspection Identification

  • Asset identification recorded
    Record the breaker, recloser, or switchgear asset ID, location, and vacuum interrupter designation being tested.
  • Test date and time recorded
    Enter the date and time the open-gap withstand test was performed.
  • Inspector and competent person identified
    Record the inspector name and the qualified/competent person overseeing the test.

Safety Controls and Test Readiness

  • Lockout-tagout applied and verified
    Verify the equipment is isolated, de-energized, and controlled under an approved lockout-tagout procedure per OSHA 1910.147.
  • Appropriate arc-flash and shock PPE in use
    Confirm PPE selection is appropriate for the test setup and voltage exposure, consistent with the site electrical safety program and NFPA 70E.
  • Test area barricaded and access controlled
    Confirm the test boundary is established, warning signs are posted, and unauthorized personnel are excluded.

Test Equipment and Setup

  • Test instrument identified and calibrated
    Record the withstand test set model, serial number, and calibration due date.
  • Test leads, probes, and grounding connections inspected
    Verify leads, clamps, and grounding connections are intact, properly rated, and free of visible damage.
  • Open-gap test configuration verified
    Confirm the vacuum interrupter contacts are fully open and the test circuit is connected across the open contacts as required by the procedure.

Withstand Test Parameters

  • Applied test voltage recorded
    Record the actual applied withstand voltage used for the open-gap test.
  • Test duration recorded
    Record the duration that voltage was applied across the open vacuum interrupter contacts.
  • Acceptance criterion documented
    Record the applicable acceptance criterion or procedure reference used for this test, including the required withstand level.

Results and Deficiencies

  • Withstand held without flashover or breakdown
    Indicate whether the vacuum interrupter withstood the applied voltage across open contacts without flashover, puncture, or dielectric breakdown.
  • Evidence of loss of vacuum observed
    Indicate whether the test result suggests loss of vacuum, such as withstand failure or abnormal discharge behavior.
  • Deficiency description and disposition
    Describe any deficiency, non-conformance, or failed interrupter and note the immediate disposition, such as remove from service, retest, or escalate for replacement.

Sign-Off

  • Corrective action completed or assigned
    Document any corrective action, work order, or follow-up required after the test.
  • Inspector signature
    Inspector attestation that the test was performed and recorded accurately.