Transformer Insulation Resistance (Megger) Test
Transformer Insulation Resistance (Megger) Test
Inspection template for recording transformer winding-to-ground and winding-to-winding insulation resistance, polarization index, test voltage, and temperature-corrected results using a megohmmeter.
Inspection Details
-
Asset identification recorded
Record transformer ID, location, nameplate rating, and serial number.
-
Inspection date and time recorded
Document when the insulation resistance test was performed.
-
Inspector name and qualification recorded
Record the technician or electrician performing the test and their qualification or certification if applicable.
-
Work order or test reference recorded
Record the maintenance work order, commissioning package, or test report reference.
-
Transformer type and configuration recorded
Record transformer type, voltage class, winding configuration, and whether the unit is energized or isolated.
Safety and Test Preconditions
-
Lockout-tagout applied and verified
Confirm the transformer is isolated, de-energized, and controlled under lockout-tagout per OSHA 1910.147 before testing.
-
Absence of voltage verified
Verify absence of voltage on all applicable terminals before connecting the megohmmeter.
-
Required PPE worn
Select all PPE used for the task, such as arc-rated clothing, voltage-rated gloves, safety glasses, and face shield as applicable.
-
Test area barricaded and controlled
Confirm the test area is restricted to authorized personnel and warning signs are posted as needed.
-
Discharge procedure completed after test
Confirm the transformer windings were discharged to ground after each test and before handling conductors.
-
Test instrument calibration current
Confirm the megohmmeter calibration or verification status is current and traceable.
Environmental and Test Conditions
-
Ambient temperature recorded
Record the ambient air temperature at the time of test.
-
Winding or oil temperature recorded
Record the transformer winding temperature or oil temperature used for temperature correction.
-
Relative humidity recorded
Record relative humidity because moisture can affect insulation resistance readings.
-
Surface condition and contamination noted
Document visible moisture, dirt, oil, or contamination on bushings, terminals, and test points.
-
Test voltage selected
Record the DC test voltage applied by the megohmmeter.
Insulation Resistance Test Results
-
Winding-to-ground insulation resistance recorded
Record the one-minute insulation resistance reading between each winding and ground.
-
Winding-to-winding insulation resistance recorded
Record the insulation resistance between applicable windings, if tested.
-
Ten-minute insulation resistance recorded
Record the ten-minute reading used to calculate polarization index.
-
Polarization index calculated
Record the polarization index as the ratio of ten-minute resistance to one-minute resistance.
-
Temperature-corrected insulation resistance recorded
Record the insulation resistance corrected to the reference temperature used by the site procedure.
Acceptance, Deficiencies, and Closeout
-
Results meet site acceptance criteria
Confirm the measured and temperature-corrected results meet the applicable site or OEM acceptance criteria.
-
Deficiencies or non-conformances documented
Describe any low readings, unstable readings, contamination, moisture ingress, or suspected insulation defects.
-
Corrective action recommended
Document recommended actions such as drying, cleaning, retesting, further diagnostics, or removal from service.
-
Photo evidence attached
Attach photos of the test setup, meter readings, nameplate, or any observed deficiencies.
-
Inspector signature
Signature of the person completing the inspection and test record.