Substation Battery Capacity Discharge Test Record
Substation Battery Capacity Discharge Test Record
Periodic inspection record for station DC battery constant-current capacity discharge testing, including cell voltages, measured ampere-hour capacity, comparison to rated capacity, and replacement decision when capacity falls below the acceptance threshold.
Inspection Details
- Inspection date and time
-
Inspector name and qualification
Record the technician or engineer performing the test and note qualification if required by site procedure.
-
Battery bank identification
Enter the substation name, battery string ID, nominal DC voltage, and associated equipment designation.
-
Reference procedure or standard
Document the governing SOP, manufacturer procedure, or IEEE-based test method used for the discharge test.
- Test purpose
Test Setup and Conditions
-
Battery bank isolated for safe testing
Verify the battery bank is isolated from normal service in accordance with site lockout-tagout and switching procedures.
-
Load bank or discharge equipment rated for test current
Confirm the discharge load and test instruments are suitable for the planned constant-current test current and duration.
- Ambient temperature at start of test
- Battery electrolyte or cell temperature at start of test
- Test start open-circuit battery voltage
Battery Bank Identification and Rating
- Manufacturer and model
-
Rated capacity at specified discharge rate
Enter the manufacturer's rated ampere-hour capacity at the applicable discharge rate and end voltage.
-
Rated discharge rate and duration
Document the discharge rate basis used for the capacity comparison, such as the site-defined constant-current test rate.
-
Acceptance threshold for capacity
Capacity below this threshold requires a replacement decision and corrective action.
Discharge Test Results
-
Constant-current discharge maintained throughout test
Verify the discharge current remained within the planned test tolerance for the full test period.
- Total discharge time achieved
- Measured ampere-hour capacity
-
Measured capacity as a percentage of rated capacity
Compare measured capacity to the rated capacity using the same discharge basis.
- Lowest cell voltage recorded during discharge
-
Any cell reached the minimum allowable voltage
Flag whether any cell or jar dropped below the site or manufacturer minimum during the test.
Cell Voltage Record
-
Cell voltage readings captured for all cells
Document individual cell or jar voltages at the required test intervals per procedure.
-
Cell voltage log attached
Attach the detailed cell-by-cell voltage sheet, data logger export, or photo of the recorded log.
-
Cells with abnormal voltage deviation identified
Note any cell showing abnormal deviation, weak performance, or evidence of imbalance requiring follow-up.
Disposition, Corrective Action, and Sign-Off
-
Battery bank passes capacity acceptance threshold
Pass only if measured capacity meets or exceeds the acceptance threshold and no critical deficiencies remain.
-
Replacement or corrective action required
Select the disposition based on test results, with replacement required when capacity falls below 90 percent.
- Inspector signature