Refrigerant Charge Verification by Subcool and Superheat
Refrigerant Charge Verification by Subcool and Superheat
Inspection template for verifying HVAC refrigerant charge using subcooling on TXV systems and superheat on fixed-orifice systems, aligned to ACCA Standard 5 quality installation procedures.
Inspection Setup and System Identification
- Equipment model, serial number, and location recorded
- Refrigerant type verified against nameplate and service data
- Metering device identified as TXV/EEV or fixed orifice
- System has operated long enough to reach stable conditions before measurement
- Outdoor and indoor ambient conditions recorded
- Manufacturer charging data or service chart available on site
Operating Conditions and Measurement Readiness
- Cooling mode confirmed for charge verification
- Indoor airflow and filters are in acceptable condition for measurement
- Suction line, liquid line, and service ports accessible for measurement
- Temperature clamps and pressure gauges calibrated or verified
- Measurement instruments zeroed and attached without leaks
TXV / EEV Systems - Subcooling Verification
- System identified as TXV/EEV controlled
- Liquid line temperature measured
- Liquid line pressure measured
- Calculated subcooling recorded
- Measured subcooling matches manufacturer target within acceptable tolerance
- Superheat not used as the primary charge verification method for this TXV/EEV system
Fixed Orifice Systems - Superheat Verification
- System identified as fixed orifice / piston / cap tube controlled
- Suction line temperature measured
- Suction pressure measured
- Calculated superheat recorded
- Measured superheat matches manufacturer target within acceptable tolerance
Final Verification and Corrective Actions
- Charge verification result accepted or rejected
- Deficiencies or non-conformances documented
- Corrective action completed or assigned
- Inspector signature captured