Protective Relay Calibration and Functional Test

Protective Relay Calibration and Functional Test

Inspection template for documenting protective relay pickup, timing, and trip verification against coordination study settings during commissioning, factory testing, or periodic maintenance.

Inspection Details

  • Inspection date and time recorded
  • Asset / relay identification matches test package
    Record relay name, device number, panel, feeder, or bay identifier.
  • Test purpose selected
  • Approved coordination study / setting sheet available at point of test

Safety Preconditions and Test Readiness

  • Lockout-tagout applied where required and verified by qualified person
  • Arc-flash boundaries, shock boundaries, and PPE selected for the task
  • Test equipment calibrated and within current calibration date
  • Secondary circuits isolated or test switches positioned to prevent unintended trip
  • Trip circuit supervision and alarm status verified before injection

Relay Identification and Visual Condition

  • Relay model, serial number, and firmware/version recorded
  • Relay enclosure, terminal blocks, and wiring show no visible damage or overheating
  • CT/PT ratios and polarity match the approved drawings
  • Target flags, LEDs, and event indications cleared before test start

Pickup, Timing, and Trip Verification

  • Overcurrent pickup value verified against setting sheet
  • Measured pickup matches expected setting within tolerance
  • Measured operating time recorded
  • Measured operating time within coordination study tolerance
  • Trip output verified to correct breaker, contactor, or lockout relay
  • Trip circuit continuity and end-to-end trip path verified
  • Additional protection elements tested

As-Left Settings and Results

  • As-left relay settings match approved coordination study
  • Final event report or test printout attached
  • Test results summary

Deficiencies and Corrective Actions

  • Any deficiency or non-conformance identified
  • Corrective action documented for each failed or out-of-tolerance item

Sign-Off

  • Inspector signature
  • Reviewer / supervisor signature