AWWA C600 Water Main Hydrostatic Test Report
AWWA C600 Water Main Hydrostatic Test Report
Inspection template for documenting acceptance testing of a new water main in accordance with ANSI/AWWA C600, including a two-hour hydrostatic hold at test pressure, allowable leakage calculation, observed leakage, and inspector sign-off.
Test Identification
-
Project name and test segment identified
Record the project name, test location, pipe segment limits, and stationing or drawing reference.
-
Test date and start time recorded
Document when the hydrostatic test began.
-
Inspector and contractor representatives identified
Record names and roles of the inspector, contractor representative, and any witnessing authority.
Main and Test Segment Details
-
Pipe material, diameter, and length recorded
Document pipe material, nominal diameter, and total test length for the segment.
-
Appurtenances and fittings included in test segment
Select all items included in the test section.
-
Test section isolated and restrained
Verify the main is isolated, restrained, and ready for pressure testing without unintended movement.
Pre-Test Readiness and Safety
-
Test equipment calibrated and suitable for test pressure
Verify gauges, pumps, hoses, and fittings are in serviceable condition and appropriate for the required pressure range.
-
Test pressure gauge reading recorded
Record the stabilized gauge reading used for the test.
-
Work area controlled and safe for inspection
Verify access control, traffic control, and PPE are in place; no unsafe conditions are present during pressurization.
Hydrostatic Test Execution
-
Test pressure maintained for required two-hour hold
Confirm the main was held at the specified test pressure for a continuous two-hour period in accordance with the acceptance procedure.
-
Start and end pressure recorded
Document the pressure at the start and end of the hold period, including any observed fluctuations.
-
Observed leakage during hold
Record the measured leakage observed during the test hold period.
Leakage Calculation and Acceptance
-
Allowable leakage calculated and documented
Record the allowable leakage calculation used for the test, including the basis and any formula inputs.
-
Observed leakage within allowable limit
Confirm the measured leakage did not exceed the allowable leakage for the test segment.
-
Test result accepted
Mark whether the water main hydrostatic test is accepted based on pressure hold and leakage criteria.
Deficiencies, Corrective Actions, and Sign-Off
-
Deficiencies or non-conformances documented
Record any leaks, pressure loss, equipment issues, or other non-conformances observed during the test.
-
Corrective actions completed or scheduled
Describe repairs, retesting requirements, or follow-up actions needed before acceptance.
-
Inspector signature
Inspector signs to confirm the record is complete and accurate.