Fire Alarm Acceptance Test - NFPA 72
Fire Alarm Acceptance Test - NFPA 72
Inspection template for fire alarm acceptance testing audits covering devices, battery calculations, and graphic annunciation in accordance with NFPA 72.
Test Identification and Preconditions
-
Project, building, and fire alarm system identified
Record the facility name, address, system type, and test scope.
-
Acceptance test date and time recorded
Capture the date and start time of the acceptance test.
-
AHJ, owner representative, and contractor present
Identify required parties present for the acceptance test.
-
Approved shop drawings, sequence of operations, and device layout available
Verify that current approved documents are on site for reference during testing.
Safety Preconditions and Test Readiness
-
Work area safe and test notifications coordinated
Verify occupants, monitoring center, and affected parties were notified before testing.
-
Test equipment calibrated and suitable for device testing
Confirm test tools are appropriate and within calibration.
-
Power and normal supervisory conditions verified before test
Confirm the system is in normal condition before initiating acceptance testing.
-
Fire alarm impairment or bypass log reviewed
Verify any impairments, bypasses, or out-of-service conditions are documented.
Control Unit, Wiring, and Power Supplies
-
Control unit enclosure, labeling, and access are compliant
Verify the fire alarm control unit is accessible, labeled, and free of physical damage.
-
Trouble, supervisory, and alarm indications operate correctly
Verify the panel displays the correct condition for alarm, trouble, and supervisory events.
-
Primary and secondary power supplies verified
Confirm normal power and standby power transfer operate as intended.
-
Field wiring, circuit supervision, and end-of-line devices acceptable
Inspect wiring integrity and supervision for initiating device circuits, notification appliance circuits, and signaling pathways.
Initiating Devices and Alarm Input Functions
-
Manual pull stations activate the correct alarm response
Test representative manual stations for proper alarm initiation.
-
Smoke detectors respond to approved test method
Verify smoke detectors operate using approved test equipment or method.
-
Heat detectors respond at expected activation point
Verify heat detectors activate when exposed to the appropriate test source.
-
Waterflow, tamper, and other supervisory inputs function correctly
Confirm sprinkler and supervisory devices transmit the proper signal type.
Notification Appliances and Graphic Annunciation
-
Audible notification appliances operate throughout the test area
Verify horns, speakers, or sounders activate as designed.
-
Visible notification appliances flash and are unobstructed
Verify strobes or other visible appliances function and are visible where required.
-
Remote annunciator displays correct point and condition information
Confirm remote annunciation mirrors the correct alarm, trouble, and supervisory conditions.
-
Graphic annunciation matches approved floor plan and device locations
Verify the graphic display or map accurately identifies alarm locations.
Battery Calculations and Standby Power
-
Battery calculation provided and matches installed load
Verify the standby battery calculation is available and reflects the installed system configuration.
-
Battery terminals, date code, and installation condition acceptable
Inspect battery condition and installation quality.
-
Standby power supports required duration without trouble
Verify the system maintains operation during standby conditions.
Final Acceptance and Closeout
-
Deficiencies and non-conformances documented with corrective actions
Record all deficiencies, non-conformances, and required corrective actions.
-
System reset to normal condition and returned to service
Verify the fire alarm system was restored to normal operation after testing.
-
Inspector signature completed
Inspector attestation that the acceptance test was completed and recorded accurately.
Ask AI
Template Studio